PF2100
Modbus Card Instruction Manual v1.1
©2011 Profire Energy Inc
Jan 5, 2012
Page 6
DIP Switch Settings
There are 4 DIP switches included on the Modbus Card v1.0 and 8 DIP switches on the Modbus Card v2.0. The default settings for these DIP Switches are shown
in Figure 3 and Figure 5 respectively. You should ensure that the DIP switches are set according to your needs. The following tables describe the DIP switch
functions:
Modbus Card v1.0
#
Function
Description
1
Baud R
ate
OFF = 9600 bps, ON = 19200 bps
NOTE: Press the reset button on the card after changing the baud rate setting
while the system is running
2
Rx to Tx Delay
OFF = 2ms, ON = 25ms
3
Unused
4
Termination
OFF = 120 Ohm Termination, ON = No Termination
NOTE: External termination with a different resistor value may be required for
best performance if cable other than Cat-5e is used.
Modbus Card v2.0
#
Function
Description
S1
-
1
Baud Rate 1
OFF = 9600 bps, ON = 19200 bps
NOTE: Press the reset button on the card after changing the baud rate setting
while the system is running
S1
-
2
Baud Rate 2
Ignored in the current firmware revision
S1
-
3
Protocol
Ignored in the current firmware revision
S1
-
4
Termination
OFF = 120 Ohm Termination, ON = No Termination
NOTE: External termination with a different resistor value may be required for
best performance if cable other than Cat-5e is used.
S2
-
1
Rx to Tx Delay 1
OFF = 2ms, ON = 25ms
S2
-
2
Rx to Tx Delay 2
OFF = 2ms, ON = 25ms
S2
-
3
Parity Enable
Ignored in the
current firmware revision
S2
-
4
Parity Odd/Even
Ignored in the current firmware revision
Figure
3
S1 S2
Figure 4